58
Field Installed Accessories
HOW TO DESIGNATE AMODEL:
E
93
96 B 250 3 ITS PD
Heater Length
(inches)
28, 36, 48, 60,
72, 84, 96, 108,
or 120
Inlet
B = Bottom
F = Front
Element Volts
F = 208
H = 240
G = 277
L = 347
P1 = 480
U1 = 600
Single Phase
J = 208
K = 240
P3 = 480
U3 = 600
Three Phase
Watts Per Foot
Per Element
100, 125, 150,
165, 187, 200,
or 250
Control Options
Refer to Pg. 60
of TPI Heat
catalog.
Factory Installed
Accessories
PD = Pedestal
DR = Receptacle
WM = Screen
Model Series
93
# of Elements
1, 2, or 3
9300 Series - Radius Front Draft Barrier Heater
• LEED and green compliance, 1 and 3 phase applications
• Industrial or commercial applications
• Standard color: Bankers Bronze (powder coated)
• Also available in other standard TPI colors and custom colors
for an additional charge
• Uni-lock construction for snap fit 2 piece installation
• Temperature control can be in-built or wall mounted
• Thermal protection by full length manual reset linear limits
• Optional accessories include: duplex receptacle, and inside or
outside corner sections for wall to wall custom fit.
• Additional charges may be incurred if changes are made after
production has begun - consult factory.
• Made in U.S.A.
Features
ETL listed up to 750 Watts
/ foot for industrial or
commercial applications.
Note: All models are suitable for International use
Product Description
Factory Installed Accessories
Standard Models
TECHNICAL INFORMATION
Height
7.5”
Depth
6.15”
Length
28” to 120” in 1’ increments
Cabinet Material
Material Gauge
Aluminum
12
Optional Controls That
Can Be Built Into Unit
Thermostat, Disconnect Switch, Transformer
(Control Section Required for Relays)
TECHNICAL INFORMATION
Air Intake
Bottom / Front
Air Discharge
Top
Min Mounting Height
3” for bottom intake / 0” for front intake
Max Watts / Foot
750
Max Allowable Amps
25 without relay, 40 with relay
Voltage / Phase
208V/240V/277V/347V,480V,600V Single Phase
208V,240V,480V,600V Three Phase
Note: If using line voltage thermostat on 1 phase heaters, you
cannot exceed 25 Amps due to Amp rating of thermostat. 347,
480, and 600V can use 30 Amps with in-built thermostat.
Note: 480V single phase units minimum 36” heated length; 600V single phase units minimum 48” heated length
347-480-600 single phase and all three phase units are built with low voltage option factory installed
Note: Extended enclosure per foot is 103 dollars.
MFG
MODEL
UNIT
LENGTH
LIST FINISHED
BACK ADDER
Heater
9328 28”
824
65
9336 36”
867
72
9348 48”
977
77
9360 60”
1085
82
9372 72”
1164
87
9384 84”
1246
93
9396 96”
1314
98
93108 108”
1378
103
93120 120”
1467
109
SUFFIX
DESCRIPTION
LIST
DR Duplex Receptacle in 4” Extended
Enclosure (not available with 120” heater)
151
PD
28” through 60” - 2 Required
151
72” through 96” - 3 Required
228
108” through 120” - 4 Required
301
WM 1/4” wire mesh under grill
$6.00
Per
foot
IDS30
30 Amp/240V Disconnect Switch
77
IDS40
40 Amp/600V Disconnect Switch
77
MFG
MODEL
DESCRIPTION
LIST
9300IC Inside Corner Section 90° or 135°
243
9300OC Outside Corner Section 90° or 135°
9300EC
Right or Left End Cap
93
MFG
MODEL
UNIT
LENGTH
LIST FINISHED
BACK ADDER
Blank Section
93BS012 12”
338
60
93BS024 24”
397
65
93BS036 36”
445
72
93BS048 48”
515
77
93BS060 60”
576
82
93BS072 72”
623
87
93BS084 84”
683
93
93BS096 96”
743
98
93BS108 108”
803
103
93BS120 120”
862
109